(A division of MANU ELECTRONICS PTY LTD) |
|||||
|
|
UIC HTU settings |
||||
|
Calibrating of
UIC's
pulse output signals
is via 3 rotary select switches (numbered 0-9) marked H (Hundreds), T (Tens) and U (Units). |
||
|
Use
small flat-bladed screwdriver,
|
|
|
Formula to calculate HTU settings
|
UIC card with STANDARD x10 pulse input multiplier |
UIC card with x50 pulse input multiplier |
||||
|
|
|
|
|
||
|
HTU = |
input pulses/Litre |
x 5 |
HTU = |
input pulses/Litre |
x 25 |
|
|
output pulses/Litre |
|
|
output pulses/Litre |
|
|
|
|
|
|||
|
e.g. to convert 20 pulses/Litre to 1 pulse/Litre: |
e.g. to convert 7.3 pulses/Litre to 1 pulse/2 Litres: |
||||
|
|
|
|
|
|
|
|
HTU = |
20 pulses/Litre |
x 5 |
HTU = |
7.3 pulses/Litre |
x 25 |
|
|
1 pulse/Litre |
|
|
0.5 pulse/Litre |
|
|
|
|
|
|
||
|
HTU = |
100 (i.e. H=1 T=0 U=0) |
HTU = |
3 6 5 (i.e. H=3 T=6 U=5) |
||
For batching with concrete
admixtures, the MES20/MES20-S 20mm
1000 pulses/Litre flowmeters are primarily used.
For pulse scaling setpoint values,
refer to the the following table (for a x10 input standard UIC card):
|
Rotary value |
UIC card |
Volume |
Final Calibration: |
|
H T U |
pulse o/p rate |
per pulse |
If the liquid collected is more than pulse value shown on computer screen, |
|
0 2 5 |
200 pulses/Litre |
5 ml/pulse |
then decrease the rotary decade set value by the same % difference. |
|
0 5 0 |
100 pulses/Litre |
10 ml/pulse |
|
|
1 0 0 |
50 pulses/Litre |
20 ml/pulse |
If the liquid collected is less than pulse value shown on computer screen, |
|
1 5 0 |
33.3 pulses/Litre |
30 ml/pulse |
then increase the rotary decade set value by the same % difference. |
|
2 5 0 |
20 pulses/Litre |
50 ml/pulse |
|
|
5 0 0 |
10 pulses/Litre |
100 ml/pulse |
Note: Final calibration can also be performed via computer software scaling. |
|
9 9 9 |
5 pulses/Litre |
200 ml/pulse |
|
|
|
|
|
||||
|
|
UIC card with STANDARD x10 pulse input multiplier |
UIC card with x50 pulse input multiplier |
|
|||
|
Pipe size |
UIC Set Value |
Output pulses per Litre |
UIC Set Value |
Output pulses per Litre |
|
|
|
(mm) |
H T U |
to PLC/computer |
H T U |
to PLC/computer |
|
|
|
25 |
3 7 5 |
1 pulse per 1 Litre |
1 8 5 |
10 pulses per 1 Litre |
|
|
|
32 |
2 3 0 |
1 pulse per 1 Litre |
|
|
|
|
|
40 |
1 5 0 |
1 pulse per 1 Litre |
|
|
|
|
|
50 |
1 0 0 |
1 pulse per 1 Litre |
5 0 0 |
1 pulse per 1 Litre |
|
|
|
65 |
0 6 0 |
1 pulse per 1 Litre |
3 0 0 |
1 pulse per 1 Litre |
|
|
|
80 |
3 6 5 |
1 pulse per 10 Litre |
|
|
|
|
|
80 |
0 7 3 |
1 pulse per 2 Litre |
3 6 5 |
1 pulse per 2 litres |
|
|
|
100 |
0 9 2 |
1 pulse per 4 Litre |
1 2 5 |
1 pulse per 1 Litre |
|
|
All values are starting reference
values for RPFS-P and are approximate only,
due to possible variations in installation
conditions e.g. due to pipe direction, water
quality etc.
Values could vary up to 10%.
| Copyright © 2007 Manu Electronics Pty Ltd. All rights reserved. |
0802/1 | |